§ 14.32.220. Appendix B amended—Fire flow requirements for buildings.  


Latest version.
  • International Fire Code Appendix B sections B102.1, B103.1, B103.2, B104.2, B105.1, B105.2 and Table B105.1 are amended; section B103.3 is replaced and sections B105.2.1, B105.2.2, Figure B105.1 and Table B105.2 are added to read as follows:

    B102.1 Definitions. For the purpose of this appendix, certain terms are defined as follows:

    FIRE-FLOW CALCULATION AREA. The gross floor area, in square feet (m ), used to determine the required fire flow. Buildings on the same lot that do not meet the setback to property line requirements of International Building Code chapter 6, Table 602, shall be treated as a single fire area.

    LIMITED WATER SUPPLY SPRINKLER SYSTEM is an integrated system of piping and listed fire protection devices. Limited water supply sprinkler system components are installed in accordance with NFPA 13, NFPA 13R or NFPA 13D as applicable to the occupancy type then connected to a water supply capable of providing the required density for the most remote four sprinkler heads.

    Definitions not added or amended will remain as provided in B102.1.

    B103.1 Decreases. Not adopted.

    B103.2 Increases. Not adopted.

    B103.3 Areas without water supply systems. Limited water supply systems may be installed in accordance with provisions set forth by the fire code official. See figure B105.1.

    B104.2 Area separation. Portions of buildings, which are separated by firewalls without openings, constructed in accordance with the International Building Code, are allowed to be considered as separate fire-flow calculation areas. Buildings in urban growth areas shall be limited to one firewall separation.

    B105.1 One- and two-family dwellings and townhouses. Not adopted.

    B105.2 Buildings other than one- and two-family dwellings. The minimum fire-flow for buildings other than one- and two-family dwellings shall be as specified in Table B105.1 and Figure B105.1. Where sprinkler systems are substituted for a reduction in construction type, the lesser construction type shall be used to determine fire flow.

    Exceptions:

    1. Buildings which require five hundred gallons per minute or less after applying the required modifications are exempt from the fire flow requirement.

    2. Buildings protected with an approved automatic fire sprinkler system installed in accordance with nationally recognized standards need only provide the required water supply for the system design, provided such systems is not required by other sections of the code.

    8105.2.1 Modifications.

    1. A reduction in required fire flow of up to fifty percent, as approved, is allowed when the building is provided with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 of the International Fire Code.

    2. Where the mitigated fire flow is less than five hundred gpm and the occupancy is not an H or an I occupancy a limited supply sprinkler system may be used.

    The fire-flow requirement shall be adjusted based on the occupancy classification as specified in Table B105.2.

    B105.2.2 Duration. Water supplies shall be capable of providing the required flow for at least one hour for flows of two thousand gallons per minute or less, for two hours for flows greater than two thousand gallons per minute, and for three hours for flows greater than three thousand gallons per minute.

    Exception: Buildings that do not exceed the square footage at the five hundred gpm requirement do not need to adjust the fire flow based on the occupancy.

    The fire-flow requirement for buildings protected throughout with an approved automatic fire detection system that includes a central station monitoring installed in accordance with the provisions of NFPA72, may be reduced an additional two hundred fifty gallons per minute.

    Figure B105.1
    Find the fire flow required based on construction type, apply surcharge or credit for occupancy type on Table B105.1.
    14-32-220-B105-1.png

    TABLE B105.1
    MINIMUM REQUIRED FIRE-FLOW

    CONSTRUCTION TYPE
    FIRE FLOW
    (GALLONS PER MINUTE)
    I A&B II-A
    III A
    IV-H.T.
    V-A
    II-B
    III-B
    V-B
    TOTAL FIRE AREA IN SQUARE FEET
    500 5,500 3,700 2,600 2,100 1,600
    750 7,800 5,000 3,500 2,700 2,000
    1,000 11,100 6,800 4,700 3,500 2,400
    1,250 15,900 9,300 6,200 4,500 2,900
    1,500 22,750 12,700 8,200 5,900 3,600
    1,750 30,200 17,000 10,900 7,900 4,800
    2,000 38,700 21,800 12,900 9,800 6,200
    2,250 48,300 24,200 17,400 12,600 7,700
    2,500 59,000 33,200 21,300 15,400 9,400
    2,750 70,900 39,700 25,500 18,400 11,300
    3,000 83,700 47,100 31,100 21,800 13,400
    3,250 97,700 54,900 35,200 25,900 15,600
    3,500 112,700 63,400 40,600 29,300 18,000
    3,750 128,700 72,400 46,400 33,500 20,600
    4,000 145,900 82,100 52,500 37,900 23,300
    4,250 164,200 92,400 59,100 42,700 26,300
    4,500 183,400 103,100 66,000 47,700 29,300
    4,700 203,700 114,600 73,300 53,000 32,600
    5,000 225,200 126,700 81,100 58,600 36,000
    5,250 247,700 139,400 89,200 65,400 39,600
    5,500 271,200 152,600 97,700 70,600 43,400
    5,750 295,900 166,500 106,500 77,000 47,400
    6,000 UNLIMITED UNLIMITED 115,800 83,700 51,500
    6,200 UNLIMITED UNLIMITED 125,500 90,600 55,700
    6,500 UNLIMITED UNLIMITED 135,500 97,900 60,200
    6,750 UNLIMITED UNLIMITED 145,800 106,800 64,800
    7,000 UNLIMITED UNLIMITED 156,700 113,200 69,600
    7,250 UNLIMITED UNLIMITED 167,900 121,300 74,600
    7,500 UNLIMITED UNLIMITED 179,400 129,600 79,800
    7,750 UNLIMITED UNLIMITED 191,400 138,300 85,100
    8,000 UNLIMITED UNLIMITED UNLIMITED UNLIMITED UNLIMITED

     

    TABLE B105.2
    OCCUPANCY FIRE FLOW MODIFIERS

    PERCENTAGE OF BASE FIRE FLOW OCCUPANCY GROUPS
    CREDITS:
    -25% S-2, I-1, I-2, I-3, R-1, R-2
    -20% E-Daycare, A-1, A-2, A-3, A-4
    -15% E, I-4
    -10% A-2, A-5, B, R-4
    SURCHARGES:
    10% S-1, M-FUEL DISPENSING
    15% H-4, S-1 AIRCRAFT REPAIR, VEHICLE REPAIR
    20% H-3
    25% H-1, H-2, H-5

     